STUDI PENGGUNAAN RELAI JARAK QUADRILATERAL PADA JARINGAN DISTRIBUSI YANG MEMILIKI PEMBANGKIT TERSEBAR

Muhammad, Rivaldi (2019) STUDI PENGGUNAAN RELAI JARAK QUADRILATERAL PADA JARINGAN DISTRIBUSI YANG MEMILIKI PEMBANGKIT TERSEBAR. Diploma thesis, Universitas Andalas.

[img]
Preview
Text (Cover dan Abstrak)
Cover & Abstrak Watermark.pdf - Published Version

Download (195kB) | Preview
[img]
Preview
Text (BAB 1)
Bab 1 Watermark.pdf - Published Version

Download (174kB) | Preview
[img]
Preview
Text (BAB V)
Bab V Watermark.pdf - Published Version

Download (166kB) | Preview
[img]
Preview
Text (Daftar Pustaka)
DAFTAR PUSTAKA Watermark.pdf - Published Version

Download (231kB) | Preview
[img] Text (Skripsi Full Text)
Tugas Akhir Watermark.pdf - Published Version
Restricted to Repository staff only

Download (1MB)

Abstract

Terhubungnya Pembangkit Tersebar (PT) ke jaringan distribusi akan mengakibatkan permasalahan terhadap sistem proteksi yang sudah ada khususnya relai arus lebih. Penambahan PT dapat meningkatkan arus nominal yang melebihi setting relai proteksi. Relai jarak bekerja berdasarkan impedansi dan tidak dipegaruhi oleh besarnya nilai arus di saluran sehingga relai jarak dapat digunakan untuk memproteksi jaringan distribusi yang memiliki pembangkit tersebar. Relai Jarak karakterisitik Mho merupakan relai jarak yang umum digunakan pada sistem proteksi. Namun relai jarak mho akan mengalami maloperasi jika gangguan memiliki impedansi yang cukup besar. Untuk itu dilakukan studi penggunaan relai jarak tipe quadrilateral sebagai solusi terhadap permasalahan sistem proteksi pada jaringan distribusi yang memiliki pembangkit tersebar. Pengujian kinerja relai jarak quadrilateral dilakukan dengan 6 skenario yaitu kondisi grid terhubung, grid terputus, variasi jumlah pembangkit tersebar, dan gangguan melalui impedansi 2 Ohm untuk kondisi grid terhubung dan grid terputus. Gangguan yang diujikan adalah gangguan 3 fasa dan antar fasa dengan lokasi gangguan pada beberapa titik saluran. Dari pengujian yang dilakukan diperoleh bahwa relai jarak quadrilateral memiliki kinerja yang baik saat digunakan pada empat skenario pertama. Relai jarak quadrilateral mengalami gagal kerja ketika gangguan yang terjadi adalah gangguan antar fasa dengan impedansi gangguan yang besar karena impedansi yang dibaca relai menjadi lebih besar dari setting, hal ini sama seperti relai jarak mho. Namun relai jarak quadrilateral masih mampu bekerja untuk impedansi gangguan yang sedikit lebih besar dari maksimum impedansi gangguan yang dapat direspon dengan benar oleh relai jarak mho. Kata Kunci: Pembangkit Tersebar (PT), Relai Jarak Quadrilateral, dan Gangguan melalui impedansi. Abstract Connection of the Distributed Generation (DG) to the distribution network cause problems to the existing protection system, especially overcurrent relays. DG can increase the nominal current which exceeds the protection relay setting. Distance relays work base on impedance and not affected by the amount of current in the network. Therefore the distance relays can be used to protect distribution networks that have distributed generation. Mho Characteristic Distance Relay is a relay that is commonly used in protection systems. But it tends to maloperated if the fault has large impedance. Therefore a quadrilateral distance relay proposed as a solution to the problems of protection systems in distribution networks that have distributed generation. Quadrilateral distance relay performance was tested using 6 scenarios, i.e. grid connected conditions, islanding operation, the variations of number of the distributed generation, and faults through 2 ohm fault resistance for grid connected and islanding condition. The faults that being tested is a three phase and phase to phase faults with location of the fault at several network points. From the tests, it was found that quadrilateral distance relays had a good performance when used in the first four scenarios. The quadrilateral distance relay fails when the fault is a large impedance phase to phase because the impedance that being detected by the relay become larger than the setting, similarly with mho distance relay. But quadrilateral distance relays can respond correctly for slightly higher fault resistance than mho distance relay. Keywords: Distributed Generation (DG), Quadrilateral Distance Relay, and fault through impedance.

Item Type: Thesis (Diploma)
Primary Supervisor: Dr. Adrianti
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Fakultas Teknik > Elektro
Depositing User: S1 Teknik Elektro
Date Deposited: 22 Jul 2019 10:29
Last Modified: 22 Jul 2019 10:29
URI: http://scholar.unand.ac.id/id/eprint/46859

Actions (login required)

View Item View Item